Permit: T00PL00838

Parcel: 132090160

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
09/12/2000 PLUMBING - GAS PRESSURE TEST Approved
06/08/2000 PLUMBING - GAS PRESSURE TEST Correction Required ADDTL COMMS - 1. NEED TO RELOCATE HOT WATER HEATER OUT OF BATHROOM NO HOT WATER HEATER ALLOW IN BATHROOM MOVE HEATER TO OUTSIDE STORAGE ROOM 2. GAS PIPING UNDERSIZE 1 REQUIRE UP TO GAS RANGE 3. NEED A.G.A. GAS VALVES ON ALL APPLIANCES 4. RUN 3/4 P&T DRAIN TO OUTSIDE AT HOT WATER HEATER 5. USE APPROVE DOUBLE WALL VENT ON HOT WATER HEATER 1 ABOVE COOLER 6. PROVIDE FRESH AIR OR STORAGE ROOM DOOR. FOR HOT WATER HEATER.
06/08/2000 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0000*