Inspection History Details
Inspection Status: Correction Required
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T00PL00175
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/08/2000 | PLUMBING - GAS PRESSURE TEST | Correction Required | ADDTL COMMS - 1. GAS PRESSURE TEST OK 2. GAS SHUT OFF VALVES OK 3. GAS WATER HTR HAS NOT BEEN INSTALLED | |
| 02/08/2000 | PLUMBING - GAS PRESSURE TEST | Partial Approval | PARTIAL APPROVAL | |
| 02/03/2000 | PLUMBING - GAS PRESSURE TEST | Correction Required | ADDTL COMMS - 1. GAS LINE IS UNDERSIZED FOR CFH RATING. GAS MUST BE 1 TO FURNACE RM. 2. SEE TABLE 12-3 UPC TO CONVERT BTU DEMAND TO CFH RATING. | |
| 02/03/2000 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0000* | |
| 01/28/2000 | PLUMBING - GAS PRESSURE TEST | Correction Required | ADDTL COMMS - 1. GAS PRESSURE TEST WAS DOWN TO ZERO LBS. MUST BE AT 10 LBS OR MORE 2. MUST PROVIDE ACCESS TO ROOF FOR INSPECTION | |
| 01/28/2000 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0000* |