Permit: T00MH00650

Parcel: 129122160


Addresses:

1133 E 32ND ST

Inspection Status: Approved

Inspection History: MOBILE HOME ELECTRICAL

Date Description Inspector Results Comments
03/06/2001 MOBILE HOME ELECTRICAL Approved IVRS - Inspection 0000*
02/12/2001 MOBILE HOME ELECTRICAL Partial Approval IVRS - Inspection 0000* LHANLEY WILL NEED OAKWOOD TO CONTACT HIM AND TELL HIM IF THIS IS A 100AMP OR 200AMP HOME. BREAKERS WILL HAVE TO BE SIZED TO THEIR SPECIFICATIONS.
( RIGHT NOW YOU HAVE 100AMP AT THE PEDISTAL AND 200AMP IN THE HOME. )
02/02/2001 MOBILE HOME ELECTRICAL Denied IVRS - Inspection 0999*
200 AMP SERVICE CONNECTED TO 100 AMP HOME
IMPROPER USE OF FITTINGS TO BOND GROUNDING ELECTRODES
PEDISTAL WILL NOT PASS INSPECTION DUE TO #2 ABOVE