Inspection History Details
Inspection Status: Approved
Inspection History: MOBILE HOME ELECTRICAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2000 | MOBILE HOME ELECTRICAL | Approved | IVRS - Inspection 0000* | |
| 09/20/2000 | MOBILE HOME ELECTRICAL | Partial Approval | IVRS - Inspection 0000* CABLE DROP OK |