Inspection History: MOBILE HOME ELECTRICAL

Date Description Inspector Results Comments
12/03/2000 MOBILE HOME ELECTRICAL Approved IVRS - Inspection 0000*
11/09/2000 MOBILE HOME ELECTRICAL Denied YOU NEED PERMIT FOR ELECTRIC PEDISTAL
NO ADDRESS ON PEDISTAL
GROUNDING ELECTRODE CONDUCTOR NOT SECURED
YOU HAVE TAKEN HOME OUT OF HUD COMPLAINCE, THIS HOME IS NOT RATED FOR 100 AMPS
NO GFCI CIRCUITS IN BATH OR KITCHEN
HAZARDOUS ELECTRIC CIRCUITS ON EXTERIOR
NE MAIN BREAKER IN SUBPANEL
08/07/2000 MOBILE HOME ELECTRICAL Not ready for Inspection IVRS - Inspection 0000*