Permit: T00MH00224

Parcel: 137054000


Addresses:

819 W UTAH ST

Inspection Status: Cancelled

Inspection History: MOBILE HOME ELECTRICAL

Date Description Inspector Results Comments
05/19/2000 MOBILE HOME ELECTRICAL Cancelled IVRS - Ri canceled
05/16/2000 MOBILE HOME ELECTRICAL Correction Required ADDTL COMMS - 1. GROUNDING ELECTRODE CONDUCTOR MUST BE CONNECTED TO THE SAME BUSS AS THE NEUTRAL CONDUTOR OR PROVIDE AN APPROPRIATELY SIZED CONDUCTOR BETWEEN THE 2 BUSSES. 2. PROVIDE A PERMANENT METALLIC ADDRESS LABEL, FASTENED WITH TWO SCREWS, ON THE MAIN METER PANEL. 3. INTERIOR PANEL IS O.K.
05/16/2000 MOBILE HOME ELECTRICAL Partial Approval PARTIAL APPROVAL