Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T00ME01540
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/05/2001 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* ALL CORRECTIONS HAVE BEEN MADE |
|
01/02/2001 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* REMOVE CONDENSATE DRAIN TRAP. SEE MANUFACTURERS NOTE AT DRAIN OUTLET PAINT EXPOSED PVC W/LATEX PAINT SPRAY ENAMEL WILL NOT BE ACCEPTED CANNOT TERMINATE DRAIN OVER THE EDGE OF THE ROOF. MUST GO TO WITHIN 6" OF THE GROUND CORRECT AND RECALL FOR FINAL |