Permit: T00ME01494

Parcel: 11006159B

Inspection Status: Closed

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/27/2007 MECHANICAL - FINAL Closed New permit issued in '02 for all units.
12/27/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0999*
INSTALL CONDENSATE DRAIN TO AN APPROVED LOCATION
CANNOT HAVE CONTROL WIRING EXPOSED, USE CONDUIT OR OTHER MEANS
MARK DATA PLEATE W/PROPER HEAT STRIP INSTALLED AND FUSE UNIT ACCORDINGLY
CANNOT USE #8 WIRE ON A 60 AMP SERVICE