Permit: T00ME01439

Parcel: 135063000


Addresses:

6950 E CALLE ORION

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/14/2001 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
05/07/2001 MECHANICAL - FINAL Denied IVRS - Inspection 0999* 1) PVC ON SMALL FURNACE TOO CLOSE TO SINGLE WALL VENT. MUST HAVE MIN. 6" CLEARANCE 2) GAS FLEX CONNECTOR NOT ADEQUATE SIZE FOR 100,000 BTU. 3) WEST CONDENSOR NOT FUSED PROPERLY SEE DATA PLATE