Permit: T00ME01359

Parcel: 127122500


Addresses:

5752 E 9TH ST


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T00ME01359

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/27/2000 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
ALL CORRECTIONS HAVE BEEN MADE
11/20/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0999*
VENT CONNECTOR NOT ALL THE WAY INTO DOUBLE WALL
CIRCUIT BREAKER NOT SIZED PROPERLY TO CONDENSOR MIN 35 AMP MAX 40 AMP
CORRECT AND RECALL FOR FINAL