Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/27/2000 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* ALL CORRECTIONS HAVE BEEN MADE |
|
| 11/20/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* VENT CONNECTOR NOT ALL THE WAY INTO DOUBLE WALL CIRCUIT BREAKER NOT SIZED PROPERLY TO CONDENSOR MIN 35 AMP MAX 40 AMP CORRECT AND RECALL FOR FINAL |