Permit: T00ME01328

Parcel: 133351180


Addresses:

8702 E BAKER ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/15/2000 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
11/17/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0999*
CONENSAE CANNOT TERMINATE INTO THE SIDE OF A WASTE VENT WITHOUT AN APPROVED FITTING, USE A SANTIARY TEE OR TERMINATE OVER THE TOP WITH A PVC TEE, PAINT EXPOSED PVC WITH LATEX PAINT, BLOCK AND CLAMP EVERY4'
THERMOSTAT WIRE MUST BE PROTECTED FROM SUN DAMAGE USE CONDUIT IF NECESSARY
BLOCK AND CLAMP ELECTRICAL CONDUIT
BLOCK AND CLAMP GAS PIPE
CORRECT AND RECALL FOR FINAL INSPECTION THIS IS WHY WE REQUIRE PREMITS AND INSPECTIONS