Permit: T00ME01310

Parcel: 127080760


Addresses:

5458 E HOLMES ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/28/2000 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
ALL CORRECTIONS HAVE BEEN MADE
11/21/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0999*
#8 WIRE IS TOO SMALL FOR 60 AMP CIRCUIT USE #6 WIRE OR 50 AMP FUSES
USE AN APPROVED FITTING WHEN TERMINATING CONDENSATE INTO THE SIDE OF A WASTE VENT
GAS FLEX CANNOT PENTRATE THE CABINET OF THE A/C EQUIPMENT
BLOCK AND CLAMP ELECTRICAL CONDUIT CORRECT AND RECALL FOR FINAL