Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T00ME01277
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/13/2000 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* ALL CORRECTIONS HAVE BEEN MADE |
|
11/06/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* 35 AMP FUSES ARE TOO LARGE FOR THE HEAT STRIP INSTALLED IF TERMINATING CONDENSATE INTO A WASTE VENT THE MIN. SIZE VENT SHALL BE 2" SEE SECTION 310.4 NOTE #2 1994 UMC MODIFIED CODES |