Permit: T00ME01201

Parcel: 131121540


Addresses:

6249 E 31ST ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/06/2000 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
WILLIAMSON WILL FAX LISTING ON FRI
ALL CORRECTIONS HAVE BEEN MADE
10/23/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0999*
NEED TO SEE LISTING ON GAS LINE USED ON ROOF FOR OUTDOOR USE
MUST HAVE AN ELECTRICAL PERMIT TO RUN NEW CIRCUIT TO A/C EQUIPMENT
USE AN APPROVED FLASHING WHERE CONDUIT PENETRATES ROOF
WHEN TERMINATING CONDENSATE OVER A WASTE VENT YOU MUST USE A TEE NOT AN ELBOW
PAINT EXPOSED PVC W/LATEX PAINT
CONTROL WIRING MUST BE PROTECTED FROM SUN DAMAGE FAX LISTING TO JAMES MILITELLO FAX # 791-4340