Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2000 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* WILLIAMSON WILL FAX LISTING ON FRI ALL CORRECTIONS HAVE BEEN MADE |
|
| 10/23/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* NEED TO SEE LISTING ON GAS LINE USED ON ROOF FOR OUTDOOR USE MUST HAVE AN ELECTRICAL PERMIT TO RUN NEW CIRCUIT TO A/C EQUIPMENT USE AN APPROVED FLASHING WHERE CONDUIT PENETRATES ROOF WHEN TERMINATING CONDENSATE OVER A WASTE VENT YOU MUST USE A TEE NOT AN ELBOW PAINT EXPOSED PVC W/LATEX PAINT CONTROL WIRING MUST BE PROTECTED FROM SUN DAMAGE FAX LISTING TO JAMES MILITELLO FAX # 791-4340 |