Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T00ME01123
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/25/2000 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* ALL CORRECTIONS HAVE BEEN MADE |
|
10/17/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* 35 AMP FUSES ARE TOO LARGE CHECK DATA PLATE USE A PROPER FITTING ON EMT INTO THE DISCONNECT. TERMINATE CONDENSATE DRAIN INTO AN APPROVED LOCATION. CANNOT DRAIN ONTO ANY HARD SURFACE TRANE UNIT PAINT EXPOSED PVC W/LATEX PAINT. TERMINATE INTO AN APPROVED LOCATION CORRECT AND RECALL FOR FINAL |