Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/24/2000 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* ALL CORRECTIONS HAVE BEEN MADE |
|
| 10/13/2000 | MECHANICAL - FINAL | Partial Approval | MAX FUSE SIZE FOR THE HEAT STRIP IS 30 AMP CORRECT AND RECALL FOR FINAL | |
| 10/06/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* 1. YOU CANNOT TERMINATE A CONDENSATE DRAIN INTO THE SIDE OF A WASTE VENT WITHOUT AN APPROVED FITTING PAINT EXPOSED PVC W/LATEX PAINT IS THERE AUX HEAT STRIP IN THIS UNIT? SCRATCH OFF THE APPROPRIATE BOX NEXT TO THE HEAT KIT INSTALLED AND FUSE UNIT ACCORDINGLY TO DATA PLATE. |