Permit: T00ME00996

Parcel: 121100630


Addresses:

4704 E SENECA ST

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/12/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0935*
WHEN TERMINATING OVER THE TOP OF A WASTE VENT YOU MUST USE A TEE, NOT AN ELBOW
STAT WIRE STILL EXPOSED TO SUN DAMAGE
I NEED TO KNOW WHO THE CONTACTOR WAS ON THIS INSTALLATION AS I CAN TRY TO PUT A STOP TO THEM DOINT INSTALLATIONS WITHOUT INSPECTIONS. PAY A REINSPECTION FEE PRIOR TO NEXT INSPECTION CORRECT AND RECALL FOR FINAL INSPECTION
10/03/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0999*
TRAP ON CONDENSATE DRAIN IS INSTALLED BACKWARDS OUTLET ON TRAP IS HIGHER THAN OUTLET ON UNIT
PAINT EXPOSED PVC W/LATEX PAINT NO SPRAY PAINT BLOCK PVC EVERY 4' WHEN TERMINATING INTO A WASTE VENT USE A TEE
GAS SHUT OFF VLAVE MUST BE WITHIN 3' OF THE APPLIANCE (UNIT)
DISCONNECT MUST BE MOUNTED TO SOMETHING RIGID
EXPOSED LOW VOLTAGE WIRE MUST BE PROTECTED FROM SUN DAMAGE
CORRECT AND RECALL FOR FINAL INSPECTION THIS IS WHY WE REQUIRE PERMITS AND INSPECTIONS