Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/25/2000 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
| 10/03/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* UNIT MINIMUN AMPS 40.6 AMPS CIR. BKR AT SERVICE ENTRANCE IS 40 AMPS FORTY AMP SERVICE TO 5 HP CONDENSER DOES NOT MEET MIMINUM |
|
| 09/22/2000 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* NO PERMIT ON SITE COMPUTER SYSTEM DOWN SINGLE WALL VENT CONNECTOR NOT PROPER CLEARANCE FROM WOOD AND DRYWALL 2. # 8 WIRE NOT LEARGE ENOUGH FOR 60 AMP CIRCUIT TO CONDENSOR |