Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/25/2000 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
10/03/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0999*
UNIT MINIMUN AMPS 40.6 AMPS CIR. BKR AT SERVICE ENTRANCE IS 40 AMPS FORTY AMP SERVICE TO 5 HP CONDENSER DOES NOT MEET MIMINUM
09/22/2000 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*
NO PERMIT ON SITE
COMPUTER SYSTEM DOWN
SINGLE WALL VENT CONNECTOR NOT PROPER CLEARANCE FROM WOOD AND DRYWALL
2. # 8 WIRE NOT LEARGE ENOUGH FOR 60 AMP CIRCUIT TO CONDENSOR