Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* CONDENSATE CANNOT ERMINATE INTO A 1 1/2" VENT IT MUST BE MIN 2" VENT LABEL CIRCUIT BREAKER |
|
| 08/25/2000 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* YOU CANNOT TERMINATE CONDENSATE INTO ANY WASTE VENT SMALLER THAN 2" THE VENT YOU ARE USING IS 1 1/2". HOWEVER I WILL LET THIS GO SINCE YOU USED A SANT TEE INSTEAD OF GOING OVER THE TOP OF THE VENT BUT YOU DO NEED TO INSTALL A VENT AFTER THE TRAP WHEN TERMINATING INTO A WASTE VENT CORRECT AND RECALL FOR FINAL |