Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/18/2000 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* 1. STILL NEED ROOF JACK ON CONDUIT PENETRATING ROOF 2. 35 AMP FUSES ARE TOO SMALL. READ UNIT DATA PLATE FOR PROPER FUSING WILL LEAVE GAS CARD RECALL FOR FINAL |
|
| 08/11/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* UNIT NOT PROPERLY FUSED GAS LINE NEEDS PRESSURE TEST AND INSPECTION DISCONNECT NOT MOUNTED TO ANYTHING PAINT PVC W/LATEX PAINT USE A ROOF JACK ON GAS PIPE THRU ROOF SEAL JOINTS ON DUCT ON ROOF USE PROPER FITTINGSON ELECTRICAL CONDUIT MUST HAVE SHUT OFF VALVE BEFORE FLEX CONN ON ROOF STRAP AND BLOCK GAS AND ELECTRICAL ON ROOF FLEX CONNECTOR ON WATER HEATER CANNOT PENETRATE ENCLOSURE NEED TO SEE VERIFICATION THAT A LICENSED CONTRACTOR DID THE WORK HAD SOUTHWEST GAS PIN GAS METER |