Permit: T00ME00590

Parcel: 130150580


Addresses:

4601 E JUAREZ ST

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/28/2000 MECHANICAL - FINAL Denied LOCKED
08/18/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0935*
PAY RE INSPECTION FEE
GAS LINE STILL NOT HOLDING PRESSURE
CONDENSATE DRAIN LINE STILL NOT BLOCKED AND CLAMPED EVERY 4"
STRAP GAS LINE TO BLOCK ON ROOF
07/12/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0999*
1. PRESSURE GAUGE IS STUCK AT 8 PSI. GS LINE HAS LOST ALL PRESSURE. USE A GUAGE THAT WORKS PROPERLY AND RETEST FOR LEAKS
2. BLOCK CONDENSATE DRAIN EVERY 4' RECALL FOR FINAL
06/12/2000 MECHANICAL - FINAL Correction Required ADDTL COMMS - 1. CANNOT HAVE A UNION IN A CONCEALED SPACE ALSO UNION IS LEAKING GAS. 2. ANY NEW GAS LINE OVER 6 LONG NEEDS A PRESSURE TEST AND INSPECTION 3. CONDENSATE DRAIN CANNOT TERMINATE INTO THE SIDE OF A WASTE VENT WITHOUT AND APPROVED FITTING 4. PAINT EXPOSED PVC WITH LATEX PAINT
06/12/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0999*