Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/28/2000 | MECHANICAL - FINAL | Denied | LOCKED | |
| 08/18/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0935* PAY RE INSPECTION FEE GAS LINE STILL NOT HOLDING PRESSURE CONDENSATE DRAIN LINE STILL NOT BLOCKED AND CLAMPED EVERY 4" STRAP GAS LINE TO BLOCK ON ROOF |
|
| 07/12/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* 1. PRESSURE GAUGE IS STUCK AT 8 PSI. GS LINE HAS LOST ALL PRESSURE. USE A GUAGE THAT WORKS PROPERLY AND RETEST FOR LEAKS 2. BLOCK CONDENSATE DRAIN EVERY 4' RECALL FOR FINAL |
|
| 06/12/2000 | MECHANICAL - FINAL | Correction Required | ADDTL COMMS - 1. CANNOT HAVE A UNION IN A CONCEALED SPACE ALSO UNION IS LEAKING GAS. 2. ANY NEW GAS LINE OVER 6 LONG NEEDS A PRESSURE TEST AND INSPECTION 3. CONDENSATE DRAIN CANNOT TERMINATE INTO THE SIDE OF A WASTE VENT WITHOUT AND APPROVED FITTING 4. PAINT EXPOSED PVC WITH LATEX PAINT | |
| 06/12/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* |