Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/18/2001 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
| 04/11/2001 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* YOU CAN NOT TERMINATE CONDENSATE INTO A VENT SMALLER THAN 2" CORRECT AND RE CALL FOR FINAL INSP. |
|
| 04/05/2001 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* 1) CANNOT TERMINATE CONDENSATE INTO A WASTE VENT SMALLER THAN 2". USE A 3/4" TEE WHEN TERMINATING OVER THE TOP OF THE VENT, NOT AN ELBOW. 2) PAINT EXPOSED PVC WITH LATEX PAINT 3) GAS FLEX CONNECTOR NOT ADEQUATE SIZE FOR 81,000 BTU. SEE TABLE 3-D-2 1994 UMC FOR PROPER SIZING |