Inspection Status: Correction Required
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/15/2000 |
MECHANICAL - FINAL |
|
Correction Required |
ADDTL COMMS - UNIT NOT PROPERLY FUSED MAX. SIZE FUSE FOR HEAT PUMP, 30 AMPS UNIT FUSED AT 50 DOES UNIT HAVE AUX HEAT SYSTEM? YES? NO? IF YES WHAT SIZE. IF IT CORRECTLY FUSED? COMPLETE DATA PLATE AND RECALL |
| 05/15/2000 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |