Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/26/2000 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* ALL CORRECTIONS HAVE BEEN MADE |
|
| 05/16/2000 | MECHANICAL - FINAL | Correction Required | ADDTL COMMS - 1. SINGLE WALL VENT CONNECTOR NEEDS 6 CLEARANCE FROM CONBUSTIBLES. 2. NEED TO SEE ELECTRICAL CONDUIT BURIED UNDER GROUND. CONDUIT FROM DISCONNECT TO CONDENSOR NEEDS TO BE BURIED MIN. 18 DEEP. 3. NEED TO SEE REFER LINE BURIED MIN 12 CORRECT AND RECALL FOR FINAL. | |
| 05/16/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* |