Permit: T00ME00352

Parcel: 133130630


Addresses:

7751 E LEE ST

Inspection Status: Correction Required

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/14/2000 MECHANICAL - FINAL Correction Required ADDTL COMMS - ALL CORRECTIONS HAVE BEEN MADE.
04/11/2000 MECHANICAL - FINAL Correction Required ADDTL COMMS - 1. ANCHOR CONDENSING UNIT TO 4X4 SLEEPERS 2. STRAP REFER LINES TO BLOCKS 3. SINGLE WALL VENT CONNECTOR NEEDS 6 MIN. CLEARANCE FROM COMBUSTIBLES. RECOMMEND USING DOUBLE WALL PIPE.
04/11/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0999*