Permit: T00ME00072

Parcel: 133430490

Inspection Status: Correction Required

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/25/2000 MECHANICAL - FINAL Correction Required ADDTL COMMS - ALL CORRECTIONS HAVE BEEN MADE NICE JOB
04/07/2000 MECHANICAL - FINAL Correction Required ADDTL COMMS - 1. CONDENSING UNIT ON NORTH SIDE HAS 40 AMP FUSES 35 AMP IS THE MAX FUSE FOR THIS UNIT 2. CONDENSING UNIT ON SOUTH SIDE NEEDS LOW VOLTAGE WIRE TO BE RAN IN CONDUIT TO PROTECT FROM SUN DAMAGE. 3. CIRCUIT BREAKERS ARE TOO LARGE AT 40 AMPS 35 IS THE MAX 4. EMT IS NOT ALLOWED TO CONTACT TH SOIL. RAISE TO 6 ABOVE GRADE RECALL FOR FINAL INSPECTION.
04/07/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0999*