Inspection Status: Correction Required
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/25/2000 |
MECHANICAL - FINAL |
|
Correction Required |
ADDTL COMMS - ALL CORRECTIONS HAVE BEEN MADE NICE JOB |
| 04/07/2000 |
MECHANICAL - FINAL |
|
Correction Required |
ADDTL COMMS - 1. CONDENSING UNIT ON NORTH SIDE HAS 40 AMP FUSES 35 AMP IS THE MAX FUSE FOR THIS UNIT 2. CONDENSING UNIT ON SOUTH SIDE NEEDS LOW VOLTAGE WIRE TO BE RAN IN CONDUIT TO PROTECT FROM SUN DAMAGE. 3. CIRCUIT BREAKERS ARE TOO LARGE AT 40 AMPS 35 IS THE MAX 4. EMT IS NOT ALLOWED TO CONTACT TH SOIL. RAISE TO 6 ABOVE GRADE RECALL FOR FINAL INSPECTION. |
| 04/07/2000 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999* |