Inspection Status: Correction Required
Inspection History: MECHANICAL - FINAL
Permit Number - T00ME00042
Inspection Description - MECHANICAL - FINAL
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2000 | MECHANICAL - FINAL | Correction Required | ADDTL COMMS - ALL CORRECTIONS HAVE BEEN MADE. | |
| 05/05/2000 | MECHANICAL - FINAL | Correction Required | ADDTL COMMS - 1. CONDENSATE DRAIN NEEDS TO TERMINATE INTO AN APPROVED FITTING. 2. AUX HEAT STRIP IS FUSED AT 60 AMPS. NUMBER 8 WIRE WILL NOT BE ACCEPTED 3. MARK A/C UNIT DATA PLATE WITH PROPER AUX. HEAT AND FUSE UNIT ACCORDINGLY. | |
| 05/05/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999$ | |
| 04/27/2000 | MECHANICAL - FINAL | Correction Required | ADDTL COMMS - NO ACCESS TO ROOF RECALL FOR INSPECTION WHEN LADDER IS AVAILABLE | |
| 04/27/2000 | MECHANICAL - FINAL | Denied | NOT HOME/DENIED |