Inspection Status: Correction Required
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/12/2000 |
MECHANICAL - FINAL |
|
Correction Required |
ADDTL COMMS - ALL CORRECTIONS HAVE BEEN MADE. |
| 05/05/2000 |
MECHANICAL - FINAL |
|
Correction Required |
ADDTL COMMS - 1. CONDENSATE DRAIN NEEDS TO TERMINATE INTO AN APPROVED FITTING. 2. AUX HEAT STRIP IS FUSED AT 60 AMPS. NUMBER 8 WIRE WILL NOT BE ACCEPTED 3. MARK A/C UNIT DATA PLATE WITH PROPER AUX. HEAT AND FUSE UNIT ACCORDINGLY. |
| 05/05/2000 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999$ |
| 04/27/2000 |
MECHANICAL - FINAL |
|
Correction Required |
ADDTL COMMS - NO ACCESS TO ROOF RECALL FOR INSPECTION WHEN LADDER IS AVAILABLE |
| 04/27/2000 |
MECHANICAL - FINAL |
|
Denied |
NOT HOME/DENIED |