Permit: T00ME00042

Parcel: 133431260


Addresses:

10117 E CHEVELON ST


Inspection Status: Correction Required

Inspection History: MECHANICAL - FINAL

Permit Number - T00ME00042

Inspection Description - MECHANICAL - FINAL

Inspection Status - Correction Required

Date Description Inspector Results Comments
05/12/2000 MECHANICAL - FINAL Correction Required ADDTL COMMS - ALL CORRECTIONS HAVE BEEN MADE.
05/05/2000 MECHANICAL - FINAL Correction Required ADDTL COMMS - 1. CONDENSATE DRAIN NEEDS TO TERMINATE INTO AN APPROVED FITTING. 2. AUX HEAT STRIP IS FUSED AT 60 AMPS. NUMBER 8 WIRE WILL NOT BE ACCEPTED 3. MARK A/C UNIT DATA PLATE WITH PROPER AUX. HEAT AND FUSE UNIT ACCORDINGLY.
05/05/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0999$
04/27/2000 MECHANICAL - FINAL Correction Required ADDTL COMMS - NO ACCESS TO ROOF RECALL FOR INSPECTION WHEN LADDER IS AVAILABLE
04/27/2000 MECHANICAL - FINAL Denied NOT HOME/DENIED