Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/21/2000 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000* | |
| 12/20/2000 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0230* GROUND THE FOLLOWING TWO 8'X5/8" GRD RODS, GAS PIPE, AND COLD WATER TO THE NEW PANEL SECURE A WRITTEN WAIVER FROM TEP FOR THE METER MOUNTED ABOVE 6'3" AND THE 1 1/2" IMC RISER |