Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/05/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* OK TO CLEAR |
|
| 12/27/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* USE ON DOOR LISTED T/RAPS CONDUIT BLOCKING EGRESS OF WROUGHT IRON AT WINDOW BOND JUNCTION BOX 250-94 |
|
| 12/14/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* INSTALL PERMANENT ADDRESS LABEL 230-70 NEC 9287 CITY ORDIN BOND BUSHING REQUIRED ON CONDUIT CONNECTORS WHERE USING REDUCING WASHERS AND CONCENTRIC KO'S 250-94 NEC CALL FOR RE INSPECTION WHEN COMPELTE |