| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/16/2001 | SIGN ELECTRIC | Approved | IVRS - Inspection 0000* | |
| 12/27/2000 | SIGN ELECTRIC | Denied | IVRS - Inspection 0999* 30 AMP BREAKER OVERSIZED FOR #12 AMP FEEDERS TO SIGN PHOTO CALL JUNCTION BOX TO BE BONDED TO EQUIPMENT GROUND |