Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T00EL02816
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/17/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*FINAL ELECTRICAL COMPLETE | |
04/12/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* CONDUIT TERMINATIONS NOT ACCEPTABLE WHEN ATTACHED TO FACE OF J BOX COVER | |
01/22/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* FLEXIBLE CORD CONNECTION OF MACHINES IS NOT PERMITTED BY THE NEC SEC 400-7 WIRING MUST BE BY A PERMANENT METHOD |
|
01/16/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* INTERMEDIATE AND ABOVE CEILING NOT FINISHED PLEASE RECALL WHEN READY |