Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/28/2000 ELECTRIC - FINAL Denied 1. NO PERMIT/INSPECTION CARD ON SITE. 2. PROVIDE PROOF OF UFER GROUND INSPECTION AND APPROVAL OR INSTALL 2 EACH 8 FT. GROUND RODS A MINIMUM OF 6 FT APART CONNECTED WITH A CONTINOUS #4 GROUND CONDUCTOR TO THE SERVICE PANEL.
12/21/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
INSPECTION BY OTHER INSPECTORS