Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T00EL02798

Parcel: 12007259B

Inspection Status: Partial Approval

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
12/07/2000 ELECTRIC - SERVICE UPGRADE Partial Approval USE 1/4" HARDWAY TO MOUNT SERVICE EQUIPMENT OK
WILL NEED METAL ADDRESS TAG OR ENGRAVED TAG
MULTIPLE CONNECTION FOR GROUNDING CONDUCTOR UNDER ONE LUG FIX PER CODE
MUST OBTAIN PERMIT FOR OTHER UNIT (HOUSE) MUST BE FINALED PRIOR TO ALL APPROVALS