Permit: T00EL02772

Parcel: 121020360


Addresses:

5449 E WAVERLY ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T00EL02772

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/08/2000 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
OK TO CLEAR
12/05/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
UNDERGROUND CURRENT CARRING CONDUTORS IN 1" CONDUIT MUST BE DERATED TO 80% 310-15B N.E.C.
(5) UNGROUNDED CONDUCTORS
60A 2P 2-6#
30A 2P 2-10#
20A 2P 1-#12 OK THWN INSULATION