Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
07/20/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*C-11 LICENSED CONTRACTOR REQUIRED. IF YOU ARE THE OWNER OCCUPANT OF A SINGLE FAMILY RESIDENCE YOU ARE ALLOWED TO DO YOU OWN WORK ONCE 2ND METER IS INVOLVED THIS DOES NOT APPLY EVEN IF RELATED. NOTE: CANNOT USE SCHEDULE 40 PVC ABOVE GROUND.
06/20/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245* 1) INSTALL GROUNDING ELECTRODE SYSTEM FOR RENTAL OR BACK APT ART 250 NECESSARY 2) PERMANENT ADDRESS AND SUB-PANEL LABELS REQUIRED. ART 230-70 NEC. #9287 CITY ORDINANCE. 3) NEUTRAL BOND AT SERVICE ENCLOSURE ONLY. INSTALL EQUIPTMENT GROUND AND SEPARATE NEUTRAL AND GROUND BAR IN MAIN HOUSE PANEL. 4) A C-11 LICENSED CONTRACTOR REQUIRED PLEASE LEAVE NAME AND PH#