Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/29/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* OK TO CLEAR |
|
| 11/24/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0230* NEET TO BRACE SERVICE RISER PIPE INSTALL TWO GROUND RODS AND BOND RODS TO GAS LINE, COLD WATER, AND TO SERVICE EQUIPMENT GROUND NEUT, BUSS 3. BOLT DOWN PIPE CLAMP 4. MARK CIRCUIT BREAKERS TO AREA SERVED RECALL WHEN READY |