Permit: T00EL02689

Parcel: 133120180


Addresses:

2120 N NELSON AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/08/2000 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
11/29/2000 ELECTRIC - FINAL Partial Approval OK CABLE DROP
OK TO CLEAR
CALL FOR RE-INSPECTION AFTER TIE OVER TO EXISITING SERVICE, ALSO NEED ACCESS TO EXISTING SERVICE
11/20/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
INSTALL BOND BUSHING ON RISER CONDUIT. NEC 250-94
NYLON TY RAPS NOT APPROVED METHOD OF STRAPPING #4 GROUNDING ELECTRODE CONDUCT OR USE APPROVED STRAPS BOND GAS PIPING 250-104 N.E.C. VERIFY WATER BOND