Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/08/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 11/29/2000 | ELECTRIC - FINAL | Partial Approval | OK CABLE DROP OK TO CLEAR CALL FOR RE-INSPECTION AFTER TIE OVER TO EXISITING SERVICE, ALSO NEED ACCESS TO EXISTING SERVICE |
|
| 11/20/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* INSTALL BOND BUSHING ON RISER CONDUIT. NEC 250-94 NYLON TY RAPS NOT APPROVED METHOD OF STRAPPING #4 GROUNDING ELECTRODE CONDUCT OR USE APPROVED STRAPS BOND GAS PIPING 250-104 N.E.C. VERIFY WATER BOND |