| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/18/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* OK TO CLEAR |
|
| 12/06/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* BOND GAS PIPING SYSTEM PROVIDE BUSHED END WHERE UF CABLE EXITS CONDUIT SUPPORT 3/4" EMT WITHIN 3' OF J-BOX 250-104B NEC 300-16 348-13 |
|