Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/07/2001 | ELECTRIC - FINAL | Denied | 1) GROUND WIRE MUST RUN UNBROKEN WITH OUT SPLICE FROM THE GROUND RODS TO THE PANEL | |
| 11/17/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* WORK TO BE DONE BY OWNER OCCUPANT OR C-11 STRAP GROUNDING ELECTRODE LICENSED CONTRACTOR RE SUPPORT UNISTRUT SUPPORT FOR RISRE CONDUIT ANCHORS PULLING OUT OF WALL USE MIN 1/4" ANCHORS 90-4 NEC INSTALL BOND BUSHING AT BOTTOM OF PANEL FOR 1" CONNECTOR AT CONCENTRIC KO 1 1/4" CONDUIT. NEC 110-12 SEAL KO BUSHING AT TOP REAR OF PANEL TO PREVENT WATER FROM ENTERING BREAKER PANEL LENGHTEN RISER HEIGHTS, SERVICE DROP MUST BE 8' ABOVE ROOF OF MOBILE HOME NEC 230-24 |