Permit: T00EL02670

Parcel: 118061700


Addresses:

1937 W MISTLETOE CI

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/07/2001 ELECTRIC - FINAL Denied 1) GROUND WIRE MUST RUN UNBROKEN WITH OUT SPLICE FROM THE GROUND RODS TO THE PANEL
11/17/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
WORK TO BE DONE BY OWNER OCCUPANT OR C-11
STRAP GROUNDING ELECTRODE LICENSED CONTRACTOR
RE SUPPORT UNISTRUT SUPPORT FOR RISRE CONDUIT ANCHORS PULLING OUT OF WALL USE MIN 1/4" ANCHORS 90-4 NEC
INSTALL BOND BUSHING AT BOTTOM OF PANEL FOR 1" CONNECTOR AT CONCENTRIC KO 1 1/4" CONDUIT. NEC 110-12
SEAL KO BUSHING AT TOP REAR OF PANEL TO PREVENT WATER FROM ENTERING BREAKER PANEL
LENGHTEN RISER HEIGHTS, SERVICE DROP MUST BE 8' ABOVE ROOF OF MOBILE HOME NEC 230-24