Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/13/2000 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000* | |
| 12/08/2000 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0245* | |
| 11/17/2000 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0245* GAS PIPING MUST BE BONDED 250-104 B NEC GROUNDING ELECTRODE CONDUCTOR TO BE UNSPLICED SEPERATE GROUNDS, NEUTRALS 250-50 NEC J-BOX APPROV 20' 1 1/4" CONDUIT FOR SUB PANEL AND BRANCH CIRCUITS IS OVERFILLED OVER 40% 10 UNGROUNDED CONDUCTORS MUST BE DE-RATED TO 50% 310-15 N.E.C. |