Permit: T00EL02667

Parcel: 127110880


Addresses:

925 N SONOITA AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
12/13/2000 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
12/08/2000 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*
11/17/2000 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*
GAS PIPING MUST BE BONDED 250-104 B NEC
GROUNDING ELECTRODE CONDUCTOR TO BE UNSPLICED
SEPERATE GROUNDS, NEUTRALS 250-50 NEC J-BOX
APPROV 20' 1 1/4" CONDUIT FOR SUB PANEL AND BRANCH CIRCUITS IS OVERFILLED OVER 40% 10 UNGROUNDED CONDUCTORS MUST BE DE-RATED TO 50% 310-15 N.E.C.