Permit: T00EL02661

Parcel: 106110180


Addresses:

3359 N FREEWAY

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/01/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
01/26/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
OK TO CLEAR
INSTALL PROPER FITTINGS ON ROOF MOUNTED LIGHTS SEALING TYPE WITH GROUT. WILL FOLLOW UP NEXT INSPECTION
01/25/2001 ELECTRIC - FINAL Not ready for Inspection ADDRESS DISCONNECT
RUN #4 GROUND FROM RODS TO NEUTRAL
DIM LIGHTS ON ROOF DOWN TO MEET CODE (OUTDOOR)
FINSIH PANEL AND INSIDE TRIM
12/12/2000 ELECTRIC - FINAL Denied ITEMS ABOVE HAVE NOT ALL BEEN CORRECTED SERVICE UPGRADE BY ELECT CONTRACTOR OK, RELEASE SUBJECT TO RECONNECT FINAL
12/11/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
CANNOT IDENTIFY WHICH BUILDING IS 4-6 LABEL ELECTRIC AT EACH BUILDING
SEAL ALL UNUSED OPENING
EXPOSED ROMEX UNPROTECTED
NEED APPROVED JUNCTION BOX FOR SPLICES
NEED COVERS FOR JUNCTION BOX
11/30/2000 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
OK TO CLEAR 3359 N FREEWAY ONLY
NEED TO CHANGE ADDRESS ON RECONNECT PERMIT AND RECALL
NEED OTHER ADDRESS ADDED TO PERMIT AND INSPECTED FOR SAFTEY
11/28/2000 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
NEED TO ADDRESS/LABEL METERS AND DISCONNECTS
CALL BACK IN RECONNECT PERMIT
11/24/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
11/24/00 BONDING JUMPER TO BONDING BUSHING
USE APPROVED AND LISTED BONDING LOCKNUTS
BONDING LOCK NUT CAN NOT BE USED WHERE CONCENTRIC KNOCKOUT APPEAR
BOND NEUTRAL AT SERVICE
USE APPROVED LUGS
CLEAN SURFACE UNDER GROUND LUG
INSERT ALL STRANDS UNDER LUG
DOUBLE LUG AT GROUNG
USE CORRECTLY IDENTIFYED CONDUTORS
BOND ALL JUNCTION BOXES AND GUTTERS 250-96
NEED REJECTION CLIPS