Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/01/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 01/26/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* OK TO CLEAR INSTALL PROPER FITTINGS ON ROOF MOUNTED LIGHTS SEALING TYPE WITH GROUT. WILL FOLLOW UP NEXT INSPECTION |
|
| 01/25/2001 | ELECTRIC - FINAL | Not ready for Inspection | ADDRESS DISCONNECT RUN #4 GROUND FROM RODS TO NEUTRAL DIM LIGHTS ON ROOF DOWN TO MEET CODE (OUTDOOR) FINSIH PANEL AND INSIDE TRIM |
|
| 12/12/2000 | ELECTRIC - FINAL | Denied | ITEMS ABOVE HAVE NOT ALL BEEN CORRECTED SERVICE UPGRADE BY ELECT CONTRACTOR OK, RELEASE SUBJECT TO RECONNECT FINAL | |
| 12/11/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* CANNOT IDENTIFY WHICH BUILDING IS 4-6 LABEL ELECTRIC AT EACH BUILDING SEAL ALL UNUSED OPENING EXPOSED ROMEX UNPROTECTED NEED APPROVED JUNCTION BOX FOR SPLICES NEED COVERS FOR JUNCTION BOX |
|
| 11/30/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* OK TO CLEAR 3359 N FREEWAY ONLY NEED TO CHANGE ADDRESS ON RECONNECT PERMIT AND RECALL NEED OTHER ADDRESS ADDED TO PERMIT AND INSPECTED FOR SAFTEY |
|
| 11/28/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* NEED TO ADDRESS/LABEL METERS AND DISCONNECTS CALL BACK IN RECONNECT PERMIT |
|
| 11/24/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 11/24/00 BONDING JUMPER TO BONDING BUSHING USE APPROVED AND LISTED BONDING LOCKNUTS BONDING LOCK NUT CAN NOT BE USED WHERE CONCENTRIC KNOCKOUT APPEAR BOND NEUTRAL AT SERVICE USE APPROVED LUGS CLEAN SURFACE UNDER GROUND LUG INSERT ALL STRANDS UNDER LUG DOUBLE LUG AT GROUNG USE CORRECTLY IDENTIFYED CONDUTORS BOND ALL JUNCTION BOXES AND GUTTERS 250-96 NEED REJECTION CLIPS |