Inspection History Details
Inspection Status: Denied
Inspection History: SIGN ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/26/2001 | SIGN ELECTRIC | Denied | THERE IS A LOCAL AMENDMENT TO THE N.E.C. SECTION 350-14 THAT DISALLOWS FLEXIBLE METAL CONDUIT AS A GROUNDING MEANS. YOU WILL NEED TO RUN A #14 AWG (OR LORGER) AND TIE IT TO ALL FLEX CONDUIT AND FITTING ON THE SECONDARY SIDE OF TRANSFORMERS IDENTIFY BREAKER FOR SIGN AT SUB PANEL |
|
| 01/26/2001 | SIGN ELECTRIC | Approved | IVRS - Inspection 0000* |