Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/22/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* OK TO CLEAR |
|
| 11/17/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* NEED MAIN BONDING JUMPER FROM GROUND TO NEUTRAL AT METER SERVICE LABEL BREAKER |
|
| 11/14/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 11/14/00 USE APPROVED JUNCTION BOX NEED GROUNDING ELECTRODE SYSTEM BOND WATER AND GAS LOOSE FITTINGS NEED BRACE CLOSER TO TOP OR GUY BACK NEED PERMANENT METAL ADDRESS LABEL NEED APPROPIATE OVERCURRENT PROTECION FOR CONDUCTORS SECURE CONDUITS WITHIN 3' OF BOX |