Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/17/2000 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection 0000* | |
| 11/14/2000 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection 0999* 11/14/00 USE APPROVED JUNCTION BOX NEED GROUNDING ELECTRODE SYSTEM BOND WATER AND GAS LOOSE FITTINGS NEED BRACE CLOSER TO TOP OR GUY BACK NEED PERMANENT METAL ADDRESS LABEL NEED APPROPIATE OVER CURRENT PROTECITON FOR CONDUTORS SECURE CONDUITS WITHIN 3' OF BOX |