Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
Permit Number - T00EL02643
Inspection Description - ELECTRIC - SERVICE RELOCATION
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/17/2000 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection 0000* | |
11/14/2000 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection 0999* 11/14/00 USE APPROVED JUNCTION BOX NEED GROUNDING ELECTRODE SYSTEM BOND WATER AND GAS LOOSE FITTINGS NEED BRACE CLOSER TO TOP OR GUY BACK NEED PERMANENT METAL ADDRESS LABEL NEED APPROPIATE OVER CURRENT PROTECITON FOR CONDUTORS SECURE CONDUITS WITHIN 3' OF BOX |