Permit: T00EL02632

Parcel: 117063090


Addresses:

115 N 3RD AV


Inspection Status: Partial Approval

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T00EL02632

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Partial Approval

Date Description Inspector Results Comments
03/08/2002 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*NOTES SERVICE WAS NEVER CLEARED TO TEP. SERVICE DROP NOT CHANGED OVER YET. OK TO CLEAR TEMP POWER.
01/29/2002 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*OK TO CLEAR FOR CROSSOVER. PLEASE RECALL WHEN FINAL CONNECTIONS ARE MADE. WE WILL NEED TO SEE THE INTERIOR FOR INSPECTION AT THE TIME.
01/27/2002 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*1.) GROUND ROD TO BE MINIMIUM 6' APART. PLEASE RECALL AFTER INSTALLATION OF GROUNDROD CORRECTLY WE CAN THEN DO A CROSS OVR WITH A FINAL INSPECTION TO FOLLOW.
01/10/2002 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*1.) COULD NOT LOCATE WATER BOND PLEASE VERFY. 2.) LOOSE FITTINGS ON INSIDE JUNCTION BOX 3.) CAN NOT LOCATE 2ND GROUND ROD PLEASE VERIFY 4.) WHAT ARE THE SPARES GOING TO FEED? WHO WAS HERE INFORMED ME HE IS RENTING. WHO IS LICENSED ELECTRICAL CONTRACTOR DOWN THE WORK?
11/01/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*1.) BONDS TO BE EXPOSED VERIFY IF GAS OR/AND WATER BONDS 2.) NEED PERMENENT METAL ADDRESS LABEL. 3.) LABEL BREAKERS 4.) IDENTIFY GROUNDED CONDUCTOR CLOSER TO WETHER HEAD. 5.) WILL NEED TO SEE JUNCTION BOX INSIDE OR SUBPANEL NEXT INSPECTION. IS THIS A RENTAL UNIT.