Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2001 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* WIRING AT NEW GUTTER OK NEED TO INSTALL REJECTION PINS ON 5-200 A DISCON'S GAS AND WATER BONDS OK VERIFY GROUNDING SYSTEM WILL NEED TO INSPECT 800 A DISCONNECT PRIOR TO ENERGIZE WILL INSPECT REST AT FINAL |