Permit: T00EL02617

Parcel: 106110180


Addresses:

3359 N FREEWAY

Inspection Status: Denied

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
12/12/2000 ELECTRIC - RECONNECT Denied NEED 1 HR GENERAL REPAIR PERMIT TO REPAIR DAMAGED DRYWALL THUR OUT
WILL NEED INSPECTIONS WHEN WORK DONE
WILL NEED LICENSED CONTRACTOR TO DO WORK
12/11/2000 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*
CAN NOT IDENTIFY WHICH BUILDING SERVICE THIS IS
EXPOSED CONDUTORS THROUGH OUT
UNAPPROVED CORD THRU WALL TO PANEL
UNPROTECTED AND EXPOSED ROMEX THROUGHTOUT
FIXTURES TO BE ATTACHED TO APPROVED JUNCTION BOXES
USE APPROVED WIRING METHODS AND EQUIPMENT FOR COOLER
USE MANUFACTURE APPROVED CORDS WITH FIXTURE NOT SPLICED CORD
FILL ALL UNUSED OPENING IN PANEL
NEED ALL SCREWS FOR JUNCTION BOX COVER
NEED BUILDING INSPECTOR TO CHECK STRUCTURE
NEED 1 HRS GENERAL REPAIR PERMIT TO REPAIR
11/08/2000 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*
SERVICE IN DILAPIDATED CONDITION NON WEATHER-PROOF ENCLOUSES WITH WATER, RUSTED CONNECTIONS IN ENCLOUSERS, WOOD THAT ENCLOUSER ATTACHED TO ROTTEN OUT, MISSING CUTTER COVERS AND ENDS, DOUBLE LUGGING. SERVICE NEED TO BE BROUGHT UP TO CODE
CITY ELECTRICAL INSPECTOR HAVING TEP DISCONECTING SERVICE DUE TO HAZARDOUS CONDITIONS. NEED LICENSED L*11 ELECTRICAL CONTRACTOR TO PULL PERMIT AND DO WORK