Permit: T00EL02591

Parcel: 136081740

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/13/2000 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
OK TO CLEAR
11/09/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
11/09/00 CHECK YOUR AMPERAGE ALLOWANCE FOR #2.
#2 IS OK FOR 125A- ON SERVICE ENTRANCE ONLY.
THE INSTALLATION HERE IS A CIRCUIT FEEDER
GROUND BOND MUST ALSO INCLUDE COLD WATER AND GAS PIPE