Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/20/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* SERVICE UPGRADE COMPLETE- FINAL SUBJECT TO COMPLETION OF PERMIT # T00ME01272 FOR A/C CLEARANCES AND CONNECTIONS |
| 04/16/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* 1) DOUBLE LUG AT GROUND BAR IN JUNCTION BOX 2) USE APPROVED FITTING AT LB-CHASE NIPPLE NOT APPROVED 3) WORKING CLEARANCE FOR A/C DISCONNECT 4) CAN NOT USE SHEET METAL SCREW FOR LUGS 250-8 5) CLEAN SURFACE UNDER LUGS 250-12 |
| 04/13/2001 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |