Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2000 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000* OK TO CLEAR |
|
| 11/28/2000 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0245* INSTALL BOND BUSHING WHERE R.W.'S ARE USED INSTALL CONDUIT CONNECTOR AND BUSHING TO PROTECT CABLE FROM ABRASION. 336-6 NEC 300-16 OK PATCH HOLE IN WALL LEFT FROM OLD SERVICE REMOVAL 110-12 N.E.C. BOND GAS PIPING 250-104 NEC |