Permit: T00EL02557

Parcel: 112074020

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
12/05/2000 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
OK TO CLEAR
11/28/2000 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*
INSTALL BOND BUSHING WHERE R.W.'S ARE USED
INSTALL CONDUIT CONNECTOR AND BUSHING TO PROTECT CABLE FROM ABRASION. 336-6 NEC 300-16
OK PATCH HOLE IN WALL LEFT FROM OLD SERVICE REMOVAL 110-12 N.E.C.
BOND GAS PIPING 250-104 NEC